RadiMationInterface.can

From RadiWiki
Jump to navigation Jump to search
The printable version is no longer supported and may have rendering errors. Please update your browser bookmarks and please use the default browser print function instead.

The RadiMationInterface.can is an interface between the RadiMation software and CANoe and CANalyser.

By inserting this file inside your CANoe/CANalyser project you are able to extract information from RadiMation using CANoe/CANalyser.

You can download the file here

Explanation of available events/functions[edit]

Test_Frequency[edit]

The current frequency of the test, in other words the frequency of the signal generator.

Parameter: mdFreqMHz

Unit parameter: MHz

Test_Carrier_Level[edit]

The carrier level of the signal generator

Parameter: mdPowerIndBm

Unit parameter: dBm

Test_Forward_Power[edit]

The measured value of the forward power.

Parameter: mdPowerIndBm

Unit parameter: dBm

Test_Reflected_Power[edit]

The measured value of the reflected power.

Parameter: mdPowerIndBm

Unit parameter: dBm

Test_Average_Field[edit]

The measured value of the average field.

Parameter: mdFieldVm

Unit parameter: V/m

Test_Calculated_Field[edit]

The calculated value of the field based on the calibration file.

Parameter: mdFieldVm

Unit parameter: V/m

Test_Measured_Current[edit]

The measured value of the current.

Parameter: mdCurrentInmA

Unit parameter: mA

Test_Sensor_Power[edit]

The measured power of by the current sensor power meter.

Parameter: mdPowerIndBm

Unit parameter: dBm

Test_Amplitude_Modulation_Internal[edit]

The modulation in the signal generator is configured as internal amplitude modulation.

Parameter1: mdFreqency

Unit parameter1: Hz

Parameter2: mdDepth

Unit parameter2: %

Information.png
Note: The modulation may not be active at this moment, Test_Modulation_On is the event called when the modulation is turned on.

Test_Amplitude_Modulation_External[edit]

The modulation in the signal generator is configured as external amplitude modulation.

Information.png
Note: The modulation may not be active at this moment, Test_Modulation_On is the event called when the modulation is turned on.

Test_Frequency_Modulation_Internal[edit]

The modulation in the signal generator is configured as internal frequency modulation.

Parameter1: mdFreqency

Unit parameter1: kHz

Parameter2: dmShift

Unit parameter2: kHz

Information.png
Note: The modulation may not be active at this moment, Test_Modulation_On is the event called when the modulation is turned on.

Test_Frequency_Modulation_External[edit]

The modulation in the signal generator is configured as external frequency modulation.

Information.png
Note: The modulation may not be active at this moment, Test_Modulation_On is the event called when the modulation is turned on.

Test_Pulse_Modulation_Internal[edit]

The modulation in the signal generator is configured as internal pulse modulation.

Parameter1: mdFreqency

Unit parameter1: kHz

Parameter2: mdWidth

Unit parameter2: %

Information.png
Note: The modulation may not be active at this moment, Test_Modulation_On is the event called when the modulation is turned on.

Test_Pulse_Modulation_External[edit]

The modulation in the signal generator is configured as external pulse modulation.

Information.png
Note: The modulation may not be active at this moment, Test_Modulation_On is the event called when the modulation is turned on.

Test_Modulation_On[edit]

The currently configured modulation is turned on.

Test_Modulation_Off[edit]

The current configured modulation is turned off.

Antenna_Movement_Started[edit]

Starting of the movement of the antenna tower with the target position of the antenna tower.

Parameter: position

Unit parameter: Meter

Antenna_Movement_Stopped[edit]

The stop position of the antenna tower.

Parameter: position

Unit parameter: Meter

Antenna_Movement_Percentage[edit]

The current percentage of the antenna tower movement from the start position to the end position

Parameter: percentage

Unit parameter: %

Antenna_Movement_Changing_Polarisation[edit]

Changing the antenna polarisation.

Parameter: target

Unit parameter: unitless

When the target is 1 the antenna is changed to horizontal.

When the target is 2 the antenna is changed to vertical.

TurnTable_Movement_Started[edit]

Starting of the movement of the turn table with the target position of the turn table.

Parameter: position

Unit parameter: Degrees

TurnTable_Movement_Stopped[edit]

The stop position of the turn table.

Parameter: position

Unit parameter: Degrees

TurnTable_Movement_Turning_Percentage[edit]

The current percentage of the turn table movement from the start position to the end position

Parameter: percentage

Unit parameter: %