<!-- Include a space to get a newline!! --> <!-- Beware of the space!! --> | <!-- Include a space to get a newline!! --> <!-- Beware of the space!! --> | ||
This switch matrix device driver can be used to control relays with {{RadiMation}}, even if no specific device driver is yet available for those relays. See RadiMation Application Note 167: [[RadiMation Application Note 167|Controlling a custom relay via the Configurable Switch Matrix driver]] for a simple example of how this device driver can be used. | |||
{{:DeviceDriverCommunicationTab}} | |||
[[Image:Screenshot configurable switch matrix configuration window.png]] | [[Image:Screenshot configurable switch matrix configuration window.png]] | ||
For all text | For all text fields the following applies: when a text field is left empty, no command is sent at that time. | ||
{{ScreenElementDescription|Device Driver| | {{ScreenElementDescription|Device Driver| | ||
{{ScreenElementDescription|Reset|Text field to specify the reset command. The command is | {{ScreenElementDescription|Reset|Text field to specify the reset command. The command is sent to the device during the test initialization.}} | ||
{{ScreenElementDescription|Init|Text field to specify the initialize command. The command is | {{ScreenElementDescription|Init|Text field to specify the initialize command. The command is sent to the device during the test initialization.}} | ||
{{ScreenElementDescription|Get ID|Text field to specify the *IDN? query. The command is | {{ScreenElementDescription|Get ID|Text field to specify the *IDN? query. The command is sent to the device during the device check.}} | ||
{{ScreenElementDescription|Returned ID|Text field to specify the expected respond to have the Get ID compared with. The string is used during the device check in case a query is specified.}} | {{ScreenElementDescription|Returned ID|Text field to specify the expected respond to have the Get ID compared with. The string is used during the device check in case a query is specified.}} | ||
{{ScreenElementDescription|Deinit|Text field to specify the deinitialize command. The command is | {{ScreenElementDescription|Deinit|Text field to specify the deinitialize command. The command is sent to the device during the test deinitialization.}} | ||
}} | }} | ||
{{ScreenElementDescription|Operation| | {{ScreenElementDescription|Operation| | ||
{{ScreenElementDescription|During Test| | {{ScreenElementDescription|During Test|Commands (one per line) sent to the device just before starting the test.}} | ||
{{ScreenElementDescription|After Test| | {{ScreenElementDescription|After Test|Commands (one per line) sent to the device after finishing the test.}} | ||
{{ScreenElementDescription|After sending perform a read and discard result|When selected the driver will perform a read after sending the command. Some | {{ScreenElementDescription|After sending perform a read and discard result|When selected the driver will perform a read after sending the command. Some devices need to be read out before | ||
sending the next command.}} | sending the next command.}} | ||
}} | }} | ||
{{ScreenElementDescription|Operation Complete| | {{ScreenElementDescription|Operation Complete| | ||
{{ScreenElementDescription|Wait for Operation Completion after sending command(s)|This will append the *OPC? to the commands being | {{ScreenElementDescription|Wait for Operation Completion after sending command(s)|This will append the *OPC? to the commands being sent.}} | ||
}} | }} | ||
[[Image:Configurable_switch_matrix_configuration_window_custom2.png]] | [[Image:Configurable_switch_matrix_configuration_window_custom2.png]] | ||
The following fields can be specified to sent commands at each event. In several of the commands a keyword can be specified, which will be replaced by the actual value. | |||
{{ScreenElementDescription|Test| | {{ScreenElementDescription|Test| | ||
{{ScreenElementDescription|Test started| | {{ScreenElementDescription|Test started|}} | ||
{{ScreenElementDescription|Test stopped| | {{ScreenElementDescription|Test stopped|}} | ||
}} | }} | ||
{{ScreenElementDescription|Signal| | {{ScreenElementDescription|Signal| | ||
{{ScreenElementDescription|Frequency changed| | {{ScreenElementDescription|Frequency changed| Keyword __freq__ will be replaced by the frequency in MHz.}} | ||
{{ScreenElementDescription|Carrier Level changed| | {{ScreenElementDescription|Carrier Level changed| Keyword __carrier__, will be replaced by the carrier level in dBm.}} | ||
}} | }} | ||
{{ScreenElementDescription|Dwell-time| | {{ScreenElementDescription|Dwell-time| | ||
{{ScreenElementDescription|Dwell-time started| | {{ScreenElementDescription|Dwell-time started|}} | ||
{{ScreenElementDescription|Dwell-time stopped| | {{ScreenElementDescription|Dwell-time stopped|}} | ||
}} | }} | ||
{{ScreenElementDescription|Modulation| | {{ScreenElementDescription|Modulation| | ||
{{ScreenElementDescription|Modulation on| | {{ScreenElementDescription|Modulation on|}} | ||
{{ScreenElementDescription|Modulation off| | {{ScreenElementDescription|Modulation off|}} | ||
}} | }} | ||
[[Image:Configurable_switch_matrix_configuration_window_custom3.png]] | [[Image:Configurable_switch_matrix_configuration_window_custom3.png]] | ||
The following fields can be specified to sent commands at each event. Depending on the event, the keyword __result__ can be used and is replaced by a value. For example: "My forward power is __result__dBm" will be replaced by: "My forward power is -3.15dBm". | |||
{{ScreenElementDescription|Measurements| | {{ScreenElementDescription|Measurements| | ||
{{ScreenElementDescription|Before Forward Power|}} | {{ScreenElementDescription|Before Forward Power|}} | ||
{{ScreenElementDescription|After Forward Power| Keyword __result__ will be replaced by measured Forward power in dBm}} | {{ScreenElementDescription|After Forward Power| Keyword __result__ will be replaced by measured Forward power in dBm.}} | ||
{{ScreenElementDescription|Before Reflected Power|}} | {{ScreenElementDescription|Before Reflected Power|}} | ||
{{ScreenElementDescription|After Reflected Power|Keyword __result__ will be replaced by measured Reflected power in dBm}} | {{ScreenElementDescription|After Reflected Power|Keyword __result__ will be replaced by measured Reflected power in dBm. }} | ||
{{ScreenElementDescription|Net Forward Power| Keyword __result__ will be replaced by measured Net power in dBm}} | {{ScreenElementDescription|Net Forward Power| Keyword __result__ will be replaced by measured Net power in dBm}} | ||
{{ScreenElementDescription|Field Sensor| Keyword __result__ will be replaced by measured Field strength in V/m}} | {{ScreenElementDescription|Field Sensor| Keyword __result__ will be replaced by measured Field strength in V/m}} | ||
| Line 64: | Line 70: | ||
[[Image:Configurable_switch_matrix_configuration_window_custom4.png]] | [[Image:Configurable_switch_matrix_configuration_window_custom4.png]] | ||
The following fields can be specified to sent commands at each event. | |||
{{ScreenElementDescription|Antenna Tower| | {{ScreenElementDescription|Antenna Tower| | ||
{{ScreenElementDescription|Antenna Tower started| | {{ScreenElementDescription|Antenna Tower started|}} | ||
{{ScreenElementDescription|Antenna Tower stopped| | {{ScreenElementDescription|Antenna Tower stopped|}} | ||
{{ScreenElementDescription|Antenna Tower changed| | {{ScreenElementDescription|Antenna Tower changed|}} | ||
{{ScreenElementDescription|Antenna Tower polarization| | {{ScreenElementDescription|Antenna Tower polarization|}} | ||
}} | }} | ||
{{ScreenElementDescription|Turntable| | {{ScreenElementDescription|Turntable| | ||
{{ScreenElementDescription|Turntable started| | {{ScreenElementDescription|Turntable started|}} | ||
{{ScreenElementDescription|Turntable stopped| | {{ScreenElementDescription|Turntable stopped|}} | ||
{{ScreenElementDescription|Turntable changed| | {{ScreenElementDescription|Turntable changed|}} | ||
}} | }} | ||
In all of the commands, it is also possible to include a keyword to insert the latest known value of another measurement value. Several keywords are available can be included in these commands. When one of these keywords is detected, it will be replaced by the corresponding value. | |||
{|class="wikitable" | |||
!keyword || inserted value | |||
|- | |||
| __freq__ || the signal generator frequency expressed in MHz | |||
|- | |||
| __freqHz__ || the signal generator frequency expressed in Hz | |||
|- | |||
| __freqkHz__ || the signal generator frequency expressed in kHz | |||
|- | |||
| __freqMHz__ || the signal generator frequency expressed in MHz | |||
|- | |||
| __freqGHz__ || the signal generator frequency expressed in GHz | |||
|- | |||
| __carrier__ || the signal generator carrier level expressed in dBm | |||
|- | |||
| __carrierdBm__ || the signal generator carrier level expressed in dBm | |||
|- | |||
| __carrierW__ || the signal generator carrier level expressed in Watt | |||
|- | |||
| __carriermW__ || the signal generator carrier level expressed in milli-Watt | |||
|- | |||
| __forward__ || the forward power expressed in dBm | |||
|- | |||
| __forwarddBm__ || the forward power expressed in dBm | |||
|- | |||
| __forwardW__ || the forward power expressed in Watt | |||
|- | |||
| __forwardmW__ || the forward power expressed in milli-Watt | |||
|- | |||
| __reflected__ || the reflected power expressed in dBm | |||
|- | |||
| __reflecteddBm__ || the reflected power expressed in dBm | |||
|- | |||
| __reflectedW__ || the reflected power expressed in Watt | |||
|- | |||
| __reflectedmW__ || the reflected power expressed in milli-Watt | |||
|- | |||
| __height__ || the height where the antenna is moving to expressed in metre | |||
|- | |||
| __heightm__ || the height where the antenna is moving to expressed in metre | |||
|- | |||
| __heightcm__ || the height where the antenna is moving to expressed in centimetre | |||
|- | |||
| __angle__ || the angle where the turntable is turning to expressed in degrees | |||
|- | |||
| __degree__ || the angle where the turntable is turning to expressed in degrees | |||
|- | |||
| __radian__ || the angle where the turntable is turning to expressed in radians | |||
|} | |||
Please note the following regarding these keywords: | |||
* the keywords are case sensitive, | |||
* the latest known value at that moment will be used, | |||
* if no value is known at all, the keyword will not be replaced, and will remain in the command, | |||
* the values are transmitted in non-scientific notation, and will use a '.' as a decimal point. | |||
[[Category:Configurable Drivers]] | [[Category:Configurable Drivers]] | ||
Latest revision as of 10:52, 4 November 2025
The Configurable Switch Matrix device driver is a Switch Matrix which is supported by RadiMation®.
This switch matrix device driver can be used to control relays with RadiMation®, even if no specific device driver is yet available for those relays. See RadiMation Application Note 167: Controlling a custom relay via the Configurable Switch Matrix driver for a simple example of how this device driver can be used.
On the Communication tab, the desired communication method can be selected and configured. Depending on the selected method, additional relevant settings are shown and can be configured.
| Selects the medium or method that should be used to communicate with the device. Depending on the capabilities of the device this can be one or more of:
Depending on the selected communication stream, additional configuration parameters can be configured. See the Communication Settings in Chapter 15, on how to configure each of these communication streams. |
For all text fields the following applies: when a text field is left empty, no command is sent at that time.
|
|
|
The following fields can be specified to sent commands at each event. In several of the commands a keyword can be specified, which will be replaced by the actual value.
|
|
|
|
|
|
|
The following fields can be specified to sent commands at each event. Depending on the event, the keyword __result__ can be used and is replaced by a value. For example: "My forward power is __result__dBm" will be replaced by: "My forward power is -3.15dBm".
|
The following fields can be specified to sent commands at each event.
|
|
|
|
In all of the commands, it is also possible to include a keyword to insert the latest known value of another measurement value. Several keywords are available can be included in these commands. When one of these keywords is detected, it will be replaced by the corresponding value.
| keyword | inserted value |
|---|---|
| __freq__ | the signal generator frequency expressed in MHz |
| __freqHz__ | the signal generator frequency expressed in Hz |
| __freqkHz__ | the signal generator frequency expressed in kHz |
| __freqMHz__ | the signal generator frequency expressed in MHz |
| __freqGHz__ | the signal generator frequency expressed in GHz |
| __carrier__ | the signal generator carrier level expressed in dBm |
| __carrierdBm__ | the signal generator carrier level expressed in dBm |
| __carrierW__ | the signal generator carrier level expressed in Watt |
| __carriermW__ | the signal generator carrier level expressed in milli-Watt |
| __forward__ | the forward power expressed in dBm |
| __forwarddBm__ | the forward power expressed in dBm |
| __forwardW__ | the forward power expressed in Watt |
| __forwardmW__ | the forward power expressed in milli-Watt |
| __reflected__ | the reflected power expressed in dBm |
| __reflecteddBm__ | the reflected power expressed in dBm |
| __reflectedW__ | the reflected power expressed in Watt |
| __reflectedmW__ | the reflected power expressed in milli-Watt |
| __height__ | the height where the antenna is moving to expressed in metre |
| __heightm__ | the height where the antenna is moving to expressed in metre |
| __heightcm__ | the height where the antenna is moving to expressed in centimetre |
| __angle__ | the angle where the turntable is turning to expressed in degrees |
| __degree__ | the angle where the turntable is turning to expressed in degrees |
| __radian__ | the angle where the turntable is turning to expressed in radians |
Please note the following regarding these keywords:
- the keywords are case sensitive,
- the latest known value at that moment will be used,
- if no value is known at all, the keyword will not be replaced, and will remain in the command,
- the values are transmitted in non-scientific notation, and will use a '.' as a decimal point.