How to measure data from the EUT using the Configurable AD Convertor device driver[edit]
This Application Note explains how a configurable AD convertor can be used to monitor an EUT. With the AD convertor, any type of signal can be monitored and plotted within RadiMation during a test.
- First the AD convertor must be configured so values can be read within RadiMation.
- Second the value must be plotted using the correct unit types.
1 Configuring the AD convertor[edit]
1.1 Specify the communication type[edit]
First the communication type must be configured for the AD convertor.
1.2 Configure the initialization of the device[edit]
Reset | The reset code that needs to be send to device. When left blank no command will be send. |
Init | The Init code that needs to be send to device. When left blank no command will be send. |
Get Id | The code that needs to be send to device to get the identification back. A common used SCPI command is *IDN?. When left blank no command will be send. |
1.3 Configure the data readout of the device[edit]
Trigger | A trigger command can be specified to request a measurement from the device. A common used SCPI is *TRG. When left blank no command will be send. |
Read Back | Different devices return different messages with measurement values. The configurable AD convertor only need the numeric value of the measurement message. There for, a regular expressions can be set in the Read Back.
A good regular expression for finding the first number in scientific notation in a text is: ([+-]?[0-9]*\.?[0-9]+([eE][+-]?[0-9]+)?) For more possibilities see the example section. |
Minimum and maximum value[edit]
Minimum and maximum can be set to limit the measured value. And to calculate the measured value to a specific unit.
Minimum value | The lowest value that can be measured with this device. The value must be the same as filled in the EUT window. |
Maximum value | The highest value that can be measured with this device. The value must be the same as filled in the EUT window. |
1.4 Examples[edit]
Received information
|
Regex
|
RadiMation Readout
|
Note
|
---|---|---|---|
U_L_N 325 | (-?[0-9.,Ee-]+)
|
325
|
Takes the first number.
|
I_L1;12.34 | ;(-?[0-9.,Ee-]+)
|
12.34
|
Takes the first number after ";".
|
THD_U_L1;;14,5 | ;;(-?[0-9.,Ee-]+)
|
14.5
|
Takes the first number after ";;".
|
AC_FREQ;Channel1;1.23E3 | ;*;(-?[0-9.,Ee-]+)
|
1230
|
Takes the first number after the appearance of a second ";".
|
Read backs can always be tested trough the "Validate Expression tool"